Check-Manual von cmciii_lcp_airout

Rittal CMC-III LCP: Air Out Temperature
Distribution offizieller Teil von Check_MK
Lizenz GPL
Unterstützte Agenten SNMP

Note: This check is obsolete, the individual temperatures (top, middle, bottom) are also available through the cmciii.temp_in_out check. This check monitors the temperature of the outflowing air of Rittal CMC-III LCP devices. Temperatures at top, middle and bottom of the device are captured, as well as the average value given by the device. No limits are set in the check, since limits are configured in the Rittal device itself. The state given by the Rittal device is taken as the state of the check as follows: If the Rittal device returns {OK}, the check is {OK}. Otherwise the check is {CRIT}. Furthermore, the lower and upper warning and critical limits configured in the device are extracted and used as limits for the average temperature read from the device.

Discovery

One service is created for each sensor.