Check manual page of cmciii_lcp_airout

Rittal CMC-III LCP: Air Out Temperature

Distribution Official part of Checkmk
License GPLv2
Supported Agents SNMP
Note: This check is obsolete, the individual temperatures (top, middle, bottom) are also available through the cmciii.temp_in_out check. This check monitors the temperature of the outflowing air of Rittal CMC-III LCP devices. Temperatures at top, middle and bottom of the device are captured, as well as the average value given by the device. No limits are set in the check, since limits are configured in the Rittal device itself. The state given by the Rittal device is taken as the state of the check as follows: If the Rittal device returns OK, the check is OK. Otherwise the check is CRIT. Furthermore, the lower and upper warning and critical limits configured in the device are extracted and used as limits for the average temperature read from the device.

Discovery

One service is created for each sensor.