Werk #14764: apc_mod_pdu_modules: total power measurement displayed at wrong scale

Component Checks & agents
Title apc_mod_pdu_modules: total power measurement displayed at wrong scale
Date Aug 30, 2022
Checkmk Edition Checkmk Raw (CRE)
Checkmk Version 2.0.0p29 2.1.0p11 2.2.0b1
Level Trivial Change
Class Bug Fix
Compatibility Compatible - no manual interaction needed

The check "apc_mod_pdu_modules" assumed power measurements to be in hundreths of kW, instead of tenths of kW as described in the device's MIB. The correct scale is now applied.