Check manual page of apc_humidity

APC Devices: Humidity

Distribution Official part of Checkmk
License GPLv2
Supported Agents SNMP
This check monitors the humidity of sensors attached to several APC devices.

You can configure lower and upper levels for CRIT and WARN (default: WARN: 40, 60 CRIT: 35, 65)

The service goes WARN or CRIT if the humidity in percent is higher than given upper levels or lower than the given lower levels. Otherwise it returns OK.

This check uses the PowerNet-MIB.

Item

The item is the sensor description of the sensor as string.

Discovery

One service is created for each available humidity sensor.