Check manual page of apc_inrow_airflow
APC InRow Cooling Devices: Airflow
| Included in | All Checkmk editions |
|---|---|
| Source Code License | Open Source |
| Supported Agents | SNMP |
The current Airflow for a InRow Cooling devices.
You can configure lower and upper levels for CRIT and WARN
(default: WARN: 500.0, 1000.0 CRIT: 200.0, 1100.0)
The service goes WARN or CRIT if the airflow is higher
than given upper levels or lower than the given lower levels.
Otherwise it returns OK.
This check uses the PowerNet-MIB. It reads the airIRRC objects of older InRow units as well as the generic cooling unit status table of newer units (e.g. InRow ACRC301S), which do not provide the airIRRC objects anymore.
Discovery
One service is created.