Check manual page of apc_netbotz_sensors_humidity
APC Netbotz Devices: Humidity Sensor
| Included in | All Checkmk editions |
|---|---|
| Source Code License | Open Source |
| Supported Agents | SNMP |
This check monitors the humidity sensors of APC Netbotz devices which support the NETBOTZV2 MIB, e.g. Netbotz 450 series, or the NETBOTZ50 MIB, e.g. Netbotz 50.
It also monitors the wireless humidity sensors (NBWS100H) of the Netbotz Rack Monitor series, e.g. Netbotz 250. Those devices report their wireless sensors via the wirelessSensorStatusTable of the PowerNet MIB instead of one of the Netbotz MIBs.
You can configure lower and upper levels for CRIT and WARN
(default: WARN: 35, 60 CRIT: 30, 65)
The service goes WARN or CRIT if the temperature is higher
than given upper levels or lower than the given lower levels.
Otherwise it returns OK.
This check uses the NETBOTZV2-MIB, the NETBOTZ50-MIB and the PowerNet-MIB.
Item
The humidity sensor identifier. For wireless sensors this is the sensor
name configured on the device, or Wireless sensor if the sensor
has no name.
Discovery
One service is created for each humdity sensor.