Check manual page of cmciii_can_current
Rittal CMC-III PU: Canbus and Current
| Included in | All Checkmk editions |
|---|---|
| Source Code License | Open Source |
| Supported Agents | SNMP |
This check monitors the state and current of the canbus ports of the
Rittal CMC-III PU unit.
No limits are set in the check, since limits are configured in the
Rittal device itself. The state given by the Rittal device is
taken as the state of the check as follows:
If the Rittal device returns OK, the check is OK. Otherwise
the check is CRIT.
Firmware versions using the MIB of firmware V3.15.20 are supported.
Item
The unit number and the internal name of the canbus port
Discovery
One service is created for each canbus port.