Rittal CMC-III LCP: Water In/Out Temperature | |
---|---|
Distribution | Official part of Checkmk |
License | GPLv2 |
Supported Agents | SNMP |
This check monitors the temperature of the inflowing and outgoing water of Rittal CMC-III LCP devices. No limits are set in the check, since limits are configured in the Rittal device itself. The state given by the Rittal device is taken as the state of the check as follows: If the Rittal device returns OK
, the check is OK
. Otherwise the check is CRIT
. Furthermore, the lower and upper warning and critical limits configured in the device are extracted and used as limimts for the temperature read from the device.
Discovery
Two services are created: {IN} and {OUT} if it detects a proper device.