Check manual page of cmciii_temp_in_out

Rittal CMC-III Units: Temperatures In/Out

Distribution Official part of Checkmk
License GPLv2
Supported Agents SNMP
This check monitors the temperatures measured by Rittal CMC-III Liquid Cooling Package Fanpacks. These units have 6 temperature sensors, 3 for inflowing air, 3 for outflowing air. This check handles each of those sensors individually while cmciii_lcp_airin and cmciii_lcp_airout handle the temperature averages of inflowing and outflowing air respectively. Limits are configured in the Rittal device itself but can be overridden. The state given by the Rittal device is taken as the state of the check as follows: If the Rittal device returns OK, the check is OK. Otherwise the check is CRIT.

Firmware versions using the MIB of firmware V3.15.20 are supported.

Item

The unit name and the name of the temperature sensor

Discovery

One service is created for each temperature sensor on all cmciii lcp fanpack units.