Learn more about the latest product updates at the Checkmk Conference #12 – live from June 16-17! Watch here

Check manual page of liebert_compressor

Liebert: Compressor

Included in All Checkmk editions
Source Code License Open Source
Supported Agents SNMP

This check monitors the head pressure of all found compressors. The service will change to WARN if the threshold of 8 bar is reached and to CRIT if the pressure is at 12 bar.

Item

The item will be the data label of the OID

Discovery

One service is created for each compressor.