Check-Manual von apc_ats_output

APC ATS: Output Power

Distribution Official part of Checkmk
Lizenz GPLv2
Unterstützte Agenten SNMP
This check monitors the output measurements of a APC Automatic Transfer Switch.

The check monitors the

- Voltage

- Power

- Current

- Load

of the switch.

The checks has configureable upper levels for voltage (default: 240, 250) and load (default: 85, 95).

The service goes WARN/CRIT if the measurements are higher than the upper levels. Otherwise the service is OK.

This check uses the PowerNet-MIB.

Item

The internal number of the power phase

Discovery

One service is created for each power phase