Check-Manual von apc_ats_output
APC ATS: Output Power
Distribution | Official part of Checkmk |
---|---|
Lizenz | GPLv2 |
Unterstützte Agenten | SNMP |
The check monitors the
- Voltage
- Power
- Current
- Load
of the switch.
The checks has configureable upper levels for voltage (default: 240, 250) and load (default: 85, 95).
The service goes WARN
/CRIT
if the measurements are higher than the upper levels.
Otherwise the service is OK
.
This check uses the PowerNet-MIB.
Item
The internal number of the power phase
Discovery
One service is created for each power phase