Check-Manual von liebert_compressor

Liebert: Compressor

Distribution Official part of Checkmk
Lizenz GPLv2
Unterstützte Agenten SNMP
This check monitors the head pressure of all found compressors. The service will change to WARN if the threshold of 8 bar is reached and to CRIT if the pressure is at 12 bar.

Item

The item will be the data label of the OID

Discovery

One service is created for each compressor.