Check-Manual von ups_socomec_out_source
Socomec UPS Device: Power Source for Output Phases | |
---|---|
Distribution | offizieller Teil von Check_MK |
Lizenz | GPL |
Unterstützte Agenten | SNMP |
Checks by which source the output phase is powered. Warns if the device reports internal maintenance bypass or bypass, goes critical during battery operation ({"On inverter"}) or when offline. Caveat: Currently, states are interpreted according to the NetVision-nv6 MIB. Other firmware versions might be incompatible. Please send us a {cmk --snmpwalk} along with a description as to how the check behaves unexpectedly in your setup.
Discovery
One service is created.